Miele PDR 928/528 SI Steam Heated Stainless Steel Professional Vented Dryer Installation Guide

Miele PDR 928/528 SI Steam Heated Stainless Steel Professional Vented Dryer

Installation requirements

The tumble dryer must only be installed and commissioned by Miele Customer Service Department or an authorised dealer
  • The tumble dryer must be installed in accordance with all relevant regulations and standards.
  • The dryer must only be operated in a room that has sufficient ventilation and which is frost-free.
Electrical connection
The electrical connection must be established by a qualified electrician.
  • The electrical connection may only be made to an electrical system provided in accordance with all appropriate local and national legislation, regulations and guidelines. Please also observe the regulations set out by your insurance provider and energy supplier, accident prevention regulations, as well as recognised codes of practice.
  • Reliable and safe operation of this tumble dryer is only ensured if it has been connected to the mains electricity supply.
The required supply voltage, power rating and fuse rating can be found on the data plate on the tumble dryer. Ensure that the supply voltage matches the voltage quoted on the data plate before establishing the electrical connection to the tumble dryer.
Connection to a supply voltage other than the one quoted on the data plate can damage the tumble dryer if the voltage is too high.
  • If more than one voltage is specified on the data plate, the tumble dryer can be converted for connection to the relevant input voltage. This conversion must be performed by the Miele Customer Service Department or by an authorised dealer. During the conversion, the wiring instructions given on the wiring diagram must be followed.
    The tumble dryer can either be hard-wired or connected using a plug-and socket connection in accordance with IEC 60309-1. For a hard-wired connection, an all-pole isolation device must be available at the installation site.
An isolation device is a switch which ensures a contact opening of more than 3 mm. These include circuit breakers, fuses and contactors (IEC/EN 60947).

If the mains supply cannot be permanently disconnected, the isolation device (including plug and socket) must be safeguarded against being switched on either unintentionally or without authorisation.
Tip: We recommend connecting the tumble dryer to the power supply via a plug and socket so that it is easier to conduct electrical safety checks (e.g. during maintenance or repair work).

  • The tumble dryer must not be connected to devices such as timers which would switch it off automatically.
If local regulations require that a residual current device (RCD) is installed, a type B residual current device (sensitive to universal current) must be used.
Steam connection

The steam connection must only be carried out by a registered installation technician. The information from the data plate, the wiring diagram and the documentation accompanying the appliance must be noted and complied with when connecting steam-heated Miele appliances.

Condensate connection

The condensate separator must be installed so that when the system is not operating, the heater bank is completely emptied. This means that no condensate may remain in the heater bank. The installation of an inverted bucket condensate trap is recommended.

Air intake/exhaust air

The tumble dryer may only be operated when the ducting has been connected properly and the room is sufficiently ventilated.

  • Accessory parts may only be fitted when expressly approved by Miele. If other parts are used, warranty, performance and product liability claims will be invalidated

Dimensions


Dimensions quoted in millimetres

Installation


Dimensions quoted in millimetres

EL   Electrical connection
D    Steam connection
K    Condensate connection
AL    Exhaust duct
ZL    Air intake
PA    Connection for equipotential bonding (optional)
XCI   XCI Box/Connector Box (optional)

Installation (standard/on concrete plinth)



Dimensions quoted in millimetres
B Drill hole/anchor point
BS Concrete plinth

Technical data

Voltage variants/electrical data
Standard connection
Supply voltage 1N AC 230 V
Frequency 50/60 Hz
Power rating 1.2 kW
Fuse rating (on site) 10 A
Minimum cross-section for connection cable 3×1.5 mm²
Cable gland M20
Steam connection
Steam overpressure 600–1000 kPa
Boiling point 165–184 °C
Mass flow, peak capacity 60 kg/h
On-site threaded union for steam (internal thread) ½” mm
Length of steam valve connection cable 500 mm

Steam valve, dirt filter and steam shut-off valve must be fitted by the customer on site.
The steam valve must be fitted in the direct vicinity of the steam connection.

Condensate connection
On-site threaded union (internal thread) ½” mm

Shut-off equipment and condensate trap must be fitted by the customer on site.

Exhaust air
Maximum nominal volume flow rate in extraction mode (PDR 9xx only) 1000 m³/h
Maximum nominal volume flow rate (PDR 5xx only) 1100 m³/h
Maximum permitted pressure loss 510 Pa
Connector on machine side (external diameter) 150 mm
Connection pipe provided on site (internal diameter) 150 mm
Maximum exhaust air temperature 80 °C
As relative humidity inside the exhaust ducting can be as high as 100 %, suitable measures must be taken to prevent a backflow of condensate into the machine.
Air intake

Standard connection: air intake from installation site
Recommended free air intake cross-section into the room:
(equivalent to 3 times the exhaust air cross-section of a machine). 531 cm²
There must be sufficient air intake to the installation site to match the air outlet volume.

Alternative connection: air intake connection directly from outdoors
Connection sleeve on machine side (internal diameter) 161 mm
Connection pipe provided on site (external diameter) 160 mm

Removing the protective cover exposes live parts. For safety reasons, a pipe must be installed from the tumble dryer’s central fresh air intake (over a minimum length of 900 mm) and secured with 2 screws.

Machine data

Machine width, total 1206 mm
Machine height, total 1640 mm
Machine depth, total 1019 mm
Niche width 1550 mm
Recommended wall spacing (up to the front edge of the machine) 1600 mm
Minimum wall spacing (up to the back edge of the lid) 500 mm
Packaging width 1390 mm
Packaging height 1766 mm
Packaging depth 1108 mm
Maximum gross volume 2719.9 l
Maximum gross weight 295.9 kg
Maximum net weight 281.3 kg
Max. floor load in operation 3171 N
Diameter of exhaust duct 150 mm
Drum diameter 1100 mm
Diameter of drum opening 520 mm
Drum depth 561 mm
Drum volume 500 l
Diameter of door opening 520 mm
Maximum door opening angle 180°
Emission sound pressure level 60 dB(A) re 20 µPa
Sound power level 70
Average heat dissipation rate into the room 6.1 MJ/h
Permissible ambient temperature range 2–40 °C

Fixing options

Fixing without plinth
  Quantity Screw size
Tensioning strips 2  
Wood screws DIN 571 (Ø × length) 2 6×40 mm
Plugs (Ø × length) 2 10×50 mm
Fixing the appliance in place is absolutely essential.
Fastenings for floating screed must be supplied by the customer on site.
Fixing to concrete plinth
  Quantity Screw size
Tensioning strips 2  
Wood screws DIN 571 (Ø × length) 2 6×40 mm
Plugs (Ø × length) 2 10×50 mm
If the tumble dryer is being fixed to a concrete plinth on site, fixing in place is absolutely essential.
Fastenings for floating screed must be supplied by the customer on site.

Options/Accessories

Concrete base (on site)
Minimum width 1200 mm
Recommended height 100 mm
Minimum height 50 mm
Minimum depth 1100 mm
The quality of the concrete and its strength must be assessed according to the machine load. The on-site concrete plinth must be fixed adequately to the floor.