Miele PG 8055 Freestanding Fresh Water Dishwasher Installation Guide

Miele PG 8055 Freestanding Fresh Water Dishwasher

Installation notes

Installation notes

For safe installation and commissioning of the dishwasher please read the installation plan, the service documentation and the operating instructions. This installation plan includes the dimensions of the appliance, the technical data and the requirements to be met on site for the installation of the dishwasher.

Installation requirements

This dishwasher must be installed by an authorized technician in accordance with the installation instructions supplied. This dishwasher must be installed in accordance with all applicable standards and guidelines, including legal requirements and health and safety regulations.

Electrical connection

Connection to the electrical supply should be in accordance with valid regulations and safety standards. The connection cable must be protected from the risk of thermal damage. We recommend connecting the dishwasher to the power supply via a suitable plug and socket as this will make it easier to carry out the electrical safety test during commissioning and after any service work. For hard-wired dishwashers, connection should be made via a suit-able mains switch with all-pole isolation, which in the off position en-sures a 3 mm gap between all open contacts. Both the main switch and the socket must be easily accessible after installation. Faulty components must only be replaced by genuine Miele ori-ginal spare parts. Only when these parts are fitted can the safety standards of the machine be guaranteed. If the connection cable is faulty it must only be replaced by a Miele approved service techni-cian to protect the user from danger.

Equipotential bonding and earthing

For added safety the dishwasher should be protected with a residual current device with a trip current of 30 mA. Equipotential bonding should be carried out if required. The screw connection point for equipotential bonding is located at the back of the dishwasher.

Water connection (without steam condenser)

The dishwasher can be plumbed in to the cold water, hot water and drainage points without a backflow protection device. The stopcock to the water supply must be easily accessible. The water supply to the dishwasher can be connected to either cold water or hot water. The machine can be plumbed in to the cold water, hot water, demineralized water and drainage points without a backflow protection device. Use the enclosed Y-piece to establish the water intake for the dishwasher (cold water) and the steam condenser. Alternatively, you can install an additional cold water line to connect the steam condenser. If hot water is not available, both intake hoses (cold and hot water) must be connected to the cold water supply via a Y-piece. The stopcock to the water supply must be easily accessible.

Environmental requirements

Condensate can build up in the area surrounding the dishwasher. Any furniture and fittings in the room must therefore be suitable for purpose. If the machine is fitted under a suitable worktop, the panel supplied must be fitted above the door aperture to protect the work-top from moisture damage.

Connecting an external dispensing system

Up to two dispensing systems for liquid cleaning agents and rinsing agents can be connected to the back of the dishwasher. Machines with integrated dispensing systems have an external connection for rinsing agents.

Liquid agents: position of external containers

The liquid agent container for external dispensing must be positioned either next to or underneath the machine only. The container may be placed on the floor or in an adjacent cabinet. Do not place the con-tainer on top of or above the machine. Make sure that the dispensing hose does not get kinked or trapped.

Appliance dimensions

Freestanding appliance

  • PG 8055
  • PG 8056 (DOS)
  • PG 8057 TD (DOS)
  • PD 8058 (DOS)
  • PG 8059 (DOS)
  • PG 8096 (DOS)
  • PG 8099 (DOS)

front plinth area, varies depending on the appliance type

built-under appliance

PG 8055 U, PG 8056 U, PG 8061 U

PG 8056 U DOS, PG 8096 U (DOS), PG 8099 U (DOS)

front plinth area, varies depending on the appliance type

built-under appliance

PG 8057 TD U, PG 8058 U, PG 8059 U

PG 8057 TD U DOS, PG 8058 U DOS, PG 8059 U DOS

Connections

Connections on the back of the appliance

  • PG 8055, KW only
  • PG 8056 (DOS)
  • PG 8061
    PG 8096 (DOS)
  • PG 8099 (DOS)
  • PG 8057 TD (DOS)
  • PG 8058 (DOS)
  • PG 8059 (DOS)
    only PG 8058 (DOS)

On-site connections

KW Cold water WW Hot water
AW Waste water EL Electrical connection
DS External dispensing, power supply connection PA Equipotential bonding
VE DI water DK Cold water for steam condeser

Technical data

Electrical connection EU, CH, CN, RU, UA, KZ  
Voltage   3N AC 400 V /

50 Hz

AC 230 V / 50 Hz
Power rating   8.9 kW 3.4 kW
Fuse rating   3 x 16 A 1 x 16 A
Mains connection cable, min. cross-section   5 x 2.5 mm² 3 x 1.5 mm²
Length of connection cable (H05(07)RN-F)   1.7 m 1.7 m
 

Electrical connection BE, NO

     
Voltage   3 AC 230 V / 50 Hz AC 230 V / 50 Hz
Power rating   7.1 kW 2.9 kW
Fuse rating   3 x 20 A 3 x 16 A
Mains connection cable, min. cross-section   3 x 1.5 mm² 3 x 1.5 mm²
Length of connection cable (H05(07)RN-F)   1.7 m 1.7 m
 

Electrical connection AU

     
Voltage 3N AC 400 V /

50 Hz

AC 230 V / 50 Hz AC 230 V / 50 Hz
Power rating 8.9 kW 5.9 kW 2.9 kW
Fuse rating 3 x 15–16 A 1 x 30–32 A 1 x 15–16 A
Mains connection cable, min. cross-section 5 x 2.5 mm² 3 x 4 mm² 3 x 1.5 mm²
Connection cable length 1.8 m 1.9 m 1.8 m

Electrical connection US, CA

Voltage 2 AC 208 V 60 Hz 3 AC 208 V 60 Hz 3 AC 240 V 60 Hz 2 AC 240 V 60 Hz
Power rating 5.8 kW 5.8 kW 5.8 kW 5.8 kW
Fuse rating 2 pole x 30 A 3 pole x 20 A 3 pole x 20 A 2 pole x 30 A
Mains connection cable, min. cross-section 3 x AWG 10

(3 x 5.2 mm²)

4 x AWG 12

(4 x 3.3 mm²)

4 x AWG 12

(4 x 3.3 mm²)

3 x AWG 10

(3 x 5.2 mm²)

Connection cable length approx. 5’9”

(1.8 m)

approx. 5’9”

(1.8 m)

approx. 5’9”

(1.8 m)

approx. 5’9”

(1.8 m)

Electrical connection NEMA L6-30 NEMA L15-20 NEMA L15-20 NEMA L6-30
  en – Technical data
Cold water    
Max. temperature 20 °C 68 °F
Max. permitted water hardness 10714 mmol/l / 60 °dH 63 gpg
Recommended flow pressure 200 kPa 29 psi
Minimum flow pressure with extended water intake 100 kPa 14.5 psi
Maximum flow pressure 1000 kPa 145 psi
Flow rate 7.5 l/min 2 gal/min
On-site threaded union in accordance with DIN 44991 (flat sealing) 3/4 inch 3/4 Male Garden Hose Thread
Inlet hose length 1.7 m 5′ 7″
Length of steam condenser inlet hose 1.7 m 5′ 7″
Hot water    
Max. temperature 65 °C 149 °F
Max. permitted water hardness 10714 mmol/l / 60 °dH 63 gpg
Recommended flow pressure 200 kPa 29 psi
Minimum flow pressure with extended water intake 40 kPa 5.8 psi
Maximum flow pressure 1000 kPa 145 psi
Flow rate 7.5 l/min 2 gal/min
On-site threaded union in accordance with DIN 44991 (flat sealing) 3/4 inch 3/4 Male Garden Hose Thread
Inlet hose length 1.7 m 5′ 7″
Length of steam condenser inlet hose 1.7 m 5′ 7″
Waste water    
Max. waste water temperature 85 °C 185 °F
Max. waste water temperature PG 8057 TD 93 °C 200 °F
Drain hose length, standard 1.5 m 4′ 9″
Drain hose, max. drainage length 4.0 m 13′ 1″
Max. drain pump delivery head from bottom edge of machine 1.0 m 3′ 3″
Max. transient flow rate 16 l/min 4.2 gal/min
On-site sleeve for drain hose (Ø x length) 22 x 30 mm 7/8″ x 1 3/16″
Drain hose (Ø) 22 mm 7/8″
Machine data    
Machine feet height adjustment 0 – 60 mm 0 – 2 3/8″
Max. net weight 62.5 kg 138 lbs
Max. floor load during operation 1200 N 1200 N
Min. access width, incl. transport pallet 670 mm 26 3/8″
Min. access depth, incl. transport pallet 740 mm 29 3/8″
Min. access height, incl. transport pallet 920 mm 36 1/4″
Sound pressure LpA, washing and drying PG 8055, PG 8056, PG 8096, PG 8099 47 dB 47 dB
Sound pressure LpA, washing and drying PG 8057 TD, PG 8058, PG 8059 45 dB 45 dB
Dispensing  
Internal dispenser pump (DOS)
Max. delivery head 1.5 m 4.9″
Length of dispenser hose, back of appliance to suction lance

External dispenser pump

ca. 1.8 m ca. 5.9″
Max. delivery head 1.5 4.9″
Length of dispenser hose, DOS module to suction lance ca. 1.8 ca. 5.9″
Length of dispenser hose, back of appliance to DOS module ca. 2.8 ca. 9.2″
Length of power cable, back of appliance to DOS module ca. 2.8 ca. 9.2
Heat dissipation rate to installation site    
From heat radiation during operation 0.35 kWh 1194 BTU
From load items whilst unloading 0.40 kWh 1365 BTU
Installation requirements    
Permitted ambient temperature 5 – 40 °C 40 – 104 °F
Max. relative humidity up to 31 °C 80 % 80 %
Rel. humidity, declining proportionally to 40 °C 50 % 50 %
Max. altitude above sea level up to 2000 m 2000 m