SIEMENS SNW2424B1125 Outdoor Load Center Instructions

SIEMENS SNW2424B1125 Outdoor Load Center Instructions

RATINGS:
125A MAXIMUM
120/240 V-, 60 HZ, 10 3W
208Y/120 V-, 60 HZ, 10 3W

FOR INSTALLATION BY A QUALIFIED PERSON IN ACCORDANCE WITH ALL LOCAL ELECTRICAL CODES AND/OR THE NATIONAL ELECTRICAL CODE ®.

SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN MAIN BREAKER IS INSTALLED. WHEN USED AS SERVICE EQUIPMENT, APPLY “SERVICE DISCONNECT” LABEL(S) TO FRONT NEXT TO APPROPRIATE BREAKER HANDLE.

WHEN USED AS SERVICE EQUIPMENT, UNUSED NEUTRAL BAR TERMINALS MAY BE USED TO TERMINATE EQUIPMENT GROUNDING WIRES IN THE COMBINATIONS INDICATED FOR EQUIPMENT GROUND BAR TERMINALS.

TO RESET BREAKERS WITH TRIPPED HANDLE POSITION BETWEEN “ON” AND “OFF”, MOVE HANDLE TO “OFF” THEN TO “ON”.

REMOVE TWISTOUTS FROM TRIM ONLY WHERE BREAKERS WILL BE INSTALLED. ALL OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES.

IMPORTANT: DO NOT ALLOW PETROLEUM BASED (HYDROCARBON) SPRAYS, CHEMICALS, SOLVENTS OR ANY PAINT TO CONTACT INTERIOR COMPONENTS. PETROLEUM BASED CHEMICALS CAN CAUSE DEGRADATION OF ELECTRICAL INSULATING MATERIALS.

DANGER
Hazardous Voltage.

Will cause death, serious injury or substantial property damage.
Turn off power supplying this equipment before working inside.

SHORT CIRCUIT CURRENT RATING

THIS PANELBOARD HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 100,000 AMPS RMS SYMMETRICAL, 120/240V-. THE ACTUAL RATING IS DEPENDENT ON THE BRANCH BREAKERS INSTALLED IN THIS PANELBOARD AND THE MAIN/FEEDER BREAKER, IF ANY INSTALLED AHEAD OF THIS PANELBOARD. THE CORRECT MAIN BREAKER/FEEDER/MAIN BREAKER/BRANCH BREAKER SERIES COMBINATIONS TO BE USED ARE LISTED IN THE TABULATION BELOW. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED IN THIS PANELBOARD MUST BE MANUFACTURED BY SIEMENS AND MUST BE OF THE CORRECT TYPE AS INDICATED IN THE TABULATION BELOW. USE OF OTHER CIRCUIT BREAKERS IN THIS EQUIPMENT MAY VOID THE WARRANTY

MAIN BREAKER (SIEMENS TYPE) MAIN/FEEDER BREAKER PANELBOARD MAIN BRANCH BREAKER RATINGAMPS
NONE USED NONE USED or
QPH, BLH, QSH
EQ8682 01? QTA, QTAN, QAF, QAFN,
QAF2, QAF2N, QFGA2, QFGA2N,
QPF, QPF2, QPF2N, QE, QE2
22,000
QSHH EQ8682 01P, QPH*, QTA, QTAN, OAF, QAFN,
QAF2, QAF2N, QAFH, QAFH2,
QFGA2, QFGA2N, QFGAH2, QPF,
QPF2, QPF2N, QPHF, QPHF2,
QE, QE2, QEH, QEH2
42,000
ED4, ED6, HQP, HBL, HQS EQ8682 01P, QPH*, QTA, QTAN, QAF,
QAFN, QAF2, QAF2N, QAFH,
QAFH2, QFGA2, QFGA2N,
QFGAH2, QPF, QPF2,
QPF2N, QPHF, QPHF2,
OE, QE2, QEH, QEH2
65,000
NDGA, NFGA, ND6, NXD6, Class J, T, R, or L Fuses QPH, BLH
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), LXD6(-A), MD6,MXD6, ND6, SND6-B, NXD6, NJJA, NJGA, NLGB, NMG, NNG, NPG, PD6, SPD6-B, PXD6, RD6, RXD6 QPH, BLH, QS
FD6, FXD6 NONE USED or OR BL, QS
NONE USED HASH, HED4, HED6, NGB EQ8682 QP, QPH*, HQP*, QTA, QTAN, QAF,
QAFN, QAF2, QAF2N, QAFH,
QAFH2, HQAF2, QFGA2, QFGA2N,
QFGAH2, HQFGA2, QPF, QPF2,
QPF2N, QPHF, QPHF2,
HQPF2, QE, QE2, QEH, QEH2
100,000
HFD6, HFXD6, HFGA, HJD6(-A), HJXD6(-A), HJGA, HLD6(-A), HLXD6(-A), HLGB, HMD6, HMXD6, HMG, HND6, SHND6-B, HNXD6, HNG, HPD6, SHPD6-B, HPXD6, HPG, HRD6, HRXD6, or Class J, T, R, or L Fuses ED4, ED6, QS
HFD6, HFXD6, 300V Class T Fuses – 200A Max NONE USED or 01? BL

Type QPH and HQP breakers installed in this panel are limited to 100 amps max. when installed on a circuit capable of delivering fault current greater than 10,000 amps.

USE COPPER OR ALUMINIUM 60°/75°C WIRE

SEE BRAEKER MARKING FOR WIRE SIZE AND TORQUE REQUIREMENTS

TERMINALS WIRE TORQUE
G, N1 2/0 – 4 AWG 110 LB-INS
NEUTRAL/GROUND BARS (USE TYPE EC2GB or EC3GB GND BAR KIT and ECNB1ON NEUTRAL BAR KIT ACC’Y) 10-14 CU/10-12 AL
8 AWG
6-4 AWG
20 LB-INS
25 LB-INS
35 LB-INS
GROUND CONDUCTORS ONLY (2)or(3) 14 AWG
(2) 12-10 AWG
20 LB-INS
20 LB-INS
N2 ECLK2N NEUTRAL LUG 2/0 – 4 AWG 110 LB-INS
ECLK1-2 NEUTRAL LUG KIT ECLK2 NEUTRAL LUG KIT 2/0 – 4 AWG
210 – 4 AWG
45 LB-INS 135 LB-INS
MAIN BREAKER TO BUS CONNECTION (1/4-20 NUT) 45 LB-INS
BONDING SCREW 45 LB-INS

ACCESSORIES

DESCRIPTION CAT. NO.
FILLER PLATE, 1″ 0F3
SUBFEED LUG KIT ECLK21 25
STANDBY PWR INTERLOCK KIT ECSBPK1 1

MAIN BREAKER KITS

DESCRIPTION CAT. NO.
100 AMP MAIN BREAKER MBK100A
125 AMP MAIN BREAKER MBK125A

CONDUIT HUBS

TRADE SIZE CAT. NO.
1 INCH ECHS100
1-1/4 INCH ECHS125
1-1/2 INCH ECHS150
2 INCH ECHS200
2-1/2 INCH ECHS250

Assembled in Mexico
© 2021 Copyright Siemens Industry, Inc. ® The National Electrical Code is a registered trademark of the National Fire Protection Association.

INSTALLATION

THE INSTALLED NEUTRALS LIMIT THIS I PANELBOARD TO 18 CIRCUITS THAT REQUIRE NEUTRAL CONNECTIONS. IF UP TO 48 CIRCUITS ARE NEEDED INSTALL THE ECNB1ON AND THEN INSTALL ECNBX KIT(S) PER SCHEMATIC.

  1. NEUTRAL BUS FOR PLUG-ON NEUTRAL CIRCUIT BREAKERS
  2. BOND WHEN REQ’D