SIEMENS SEA45.5 Current valve Instructions

SIEMENS SEA45.5 Current valve Instructions

Dimension

Ambient temperature max. 60°C (otherwise load current must be reduced as specified in data sheet N4937!). In control panels forced ventilation by means of a fan is required. Ensure the min. distances between devices

Instruction

G System potential (SELV)
AC 24 V
Y1 Pulse/pause control signal
AC 24 V
L Load input (phase)
Q Load output
N Neutral
PE Protective earth (optional)

AC 100 … 230 V (L1 – N, L2 – N, L3 – N)

AC 100 … 400 V (L1 – L2, L1 – L3, L2 – L3):

AC 100 … 400 V (L1 – L2, L1 – L3, L2 – L3)

AC 100 … 400 V (L1 – L2, L1 – L3, L2 – L3):

F… Overcurrent trip
FF Fast-acting fuse
K… Safety loop (e.g. safety limit thermostat,
high limit cut-out)
R… Load