Panasonic CS-RU18YKA Air Conditioner Instruction Manual

Operating Instructions
Air Conditioner
Model No.

Indoor Unit
CS-RU18YKA
CS-RU24YKA
Outdoor Unit
CU-RU18YKA
CU-RU24YKA

Operating Instructions

Air Conditioner
Before operating the unit, please read these operating instructions thoroughly and keep them for future reference.
Before installation, the installer should:
Read the Installation Instructions, then request the customer to keep them for future reference.
Remove the remote control packed with the indoor unit.
If the equipment is transferred to a new user or delivered to a recycling plant, be sure also to hand over the manual.

A new built-in Network Adaptor that allows you to control your air conditioner unit operation from anywhere.

Use the remote control within 8 m from the remote control receiver on the indoor unit.

Quick Guide

Inserting the batteries

  1. Pull out the back cover of the remote control.
  2. Insert AAA or R03 batteries.
  3.  Close the cover.

A Clock setting

  1. Press then press to set the time.
    • Press for approximately 5 seconds to show the time as 12-hour (am/ pm) or 24-hour.
  2. Press to confi rm.

Thank you for purchasing Panasonic Air Conditioner.

Accessories

  • Remote control
  • AAA or R03 batteries × 2
  • Remote control holder
  • Screws for remote control holder × 2

The illustrations in this manual are for explanation purposes only and may differ from the actual unit. They are subject to change without notice.

B Basic operation

  1. Press to start/ stop the operation.
    • When the unit is ON, OFF disappears from the remote control display.
  2. Press MODE to select the desired mode.
  3. Press TEMP UP, TEMP DOWN to select the desired temperature.

Selection range: 16.0 °C ~ 30.0 °C / 60 °F ~ 86 °F.
• Press for approximately 10 seconds to show the temperature as °C or °F.

Safety Precautions

To prevent personal injury, injury to others, or property damage, please comply with the following:
Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classifi ed as below:
This appliance is not intended for accessibility by the general public.

WARNING This sign warns of death or serious injury.
CAUTION This sign warns of injury or damage to property.

The instructions to be followed are classifi ed by the following symbols:

This symbol denotes an action that is PROHIBITED.

These symbols denote actions COMPULSORY.

WARNING

Indoor unit and outdoor unit

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Please consult an authorized dealer or specialist to clean the internal parts, and repair, install, remove, disassemble and reinstall the unit. Improper installation and handling will cause leakage, electric shock, or fire.
Confi rm with authorized dealer or specialist on the usage of any specifi ed refrigerant type. Using refrigerant types other than the specifi ed may cause product damage, burst, injury, etc.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
Any unfi t method or using incompatible material may cause product damage, burst, and serious injury.
Do not install the unit in a potentially explosive or flamiable atmosphere.
Failure to do so could result in fi re.
Do not insert your fi fingers or other objects into the air conditioner indoor or outdoor unit, rotating parts may cause injury.
Do not touch the outdoor unit during lightning, it may cause electric shock.
Do not expose yourself directly to cold air for a long period to avoid excess cooling.
Do not sit or step on the unit, you may fall down accidentally.

Remote control

Do not allow infants and small children to play with the remote control to prevent them from accidentally swallowing the batteries.

Power supply

Do not use a modifi ed cord, joint cord, extension cord, or unspecifi ed cord to prevent overheating and fi re.
To prevent overheating, fi re or electric shock:

  • Do not share the same power outlet with other equipment.
  • Do not operate with wet hands.
  • Do not over-bend the power supply cord.
  • Do not operate or stop the unit by inserting or pulling out the power plug.

If the supply cord is damaged, it must be replaced by the manufacturer, service agent, or similarly qualifi ed persons in order to avoid a hazard.
It is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB)  or Residual Current Device (RCD) to prevent electric shock or fire.

To prevent overheating, fi re or electric shock:

  • Insert the power plug properly.
  • Dust on the power plug should be periodically wiped with a dry cloth.

Stop using the product if any abnormality/ failure occurs and disconnect the power plug or turn off the power switch and breaker.
(Risk of smoke/fi re/electric shock)

Examples of abnormality/failure

  • The ELCB trips frequently.
  • A burning smell is observed.
  • Abnormal noise or vibration of the unit is observed.
  • Water leaks from the indoor unit.
  • The power cord or plug becomes abnormally hot.
  • Fan speed cannot be controlled.
  • The unit stops running immediately even if it is switched on for operation.
  • The fan does not stop even if the operation is stopped.

Contact your local dealer immediately for maintenance/repair.

Replacement or installation of power plugs shall be performed by authorized/qualifi ed personnel only. The wires in this mains lead are colored in accordance with the following code:

Wiring color may vary depending on a country’s wiring code’s standard.

This equipment must be earthed to prevent electrical shock or fi re.
Prevent electric shock by switching off the power supply and unplugging:
– Before cleaning or servicing,
– When extended non-use, or
– During abnormally strong lightning activity.

CAUTION

The indoor unit and outdoor unit

Do not wash the indoor unit with water, benzine, thinner, or scouring powder to avoid damage or corrosion to the unit.
Do not use for the preservation of precise equipment, food, animals, plants, artwork, or other objects. This may cause quality deterioration, etc.
Do not use any combustible equipment in front of the airfl ow outlet to avoid fi re propagation.
Do not expose plants or pets directly to airfl ow to avoid injury, etc.
Do not touch the sharp aluminum fi n, sharp parts may cause injury.

Do not switch ON the indoor unit when waxing the floor. After waxing, aerate the room properly before operating the unit.
Do not install the unit in oily and smoky areas to prevent damage to the unit.
Do not dismantle the unit for cleaning purposes to avoid injury.
Do not step onto an unstable bench when cleaning the unit to avoid injury.
Do not place a vase or water container on the unit. Water may enter the unit and degrade the insulation. This may cause an electric shock.
Do not open windows or doors for a long time during operation, it may lead to ineffi cient power usage and uncomfortable temperature changes.
Prevent water leakage by ensuring the drainage pipe is:
– Connected properly,
– Kept clear of gutters and containers, or
– Not immersed in water
After a long period of use or use with any combustible equipment, aerate the room regularly.
After a long period of use, make sure the installation rack does not deteriorate to prevent the unit from falling down.

Remote control
Do not use rechargeable (Ni-Cd) batteries. It may damage the remote control.
To prevent malfunction or damage of the remote control:
• Remove the batteries if the unit is not going to be used for a long period of time.
• New batteries of the same type must be inserted following the polarity stated.
Power supply
Do not disconnect the plug by pulling the cord to prevent electric shock.
nanoe™-G generator
Do not touch the sharp pin which may cause injury.

Safety Precautions

WARNING

This appliance is filled with R32 (mild flammable refrigerant).
If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.
The indoor unit and outdoor unit
The appliance shall be installed, and/or operated in a room with a floor area larger than Amin (m²) and keep away from ignition sources,
such as heat/sparks/open flame or hazardous areas such as gas appliances, gas cooking, reticulated gas supply systems, or electric
cooking appliances, etc. (Refer to Table A of Installation instructions table for Amin (m²))

Be aware that refrigerant may not contain an odor, highly recommended to ensure suitable flammable refrigerant gas detectors are present, operating, and able to warn of a leak.
Keep any required ventilation openings clear of obstruction.

Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, flame, sparks, or other sources of ignition.
Else it may explode and cause injury or death.

Precaution for using R32 refrigerant
The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models.

Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation, and service tools are special.
Especially, when replacing a refrigerant R22 a model with a new refrigerant R32 model, always replace the conventional piping and
fl are nuts with the R32 and R410A piping and fl are nuts on the outdoor unit side.
For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.

The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have different charging port thread diameters to prevent erroneous charging with refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 1/2 inch.]

Must always ensure that foreign matter (oil, water, etc.) does not enter the piping. Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
  • The operation, maintenance, repairing, and refrigerant recovery should be carried out by trained and certifi ed personnel in the use of flammable refrigerants and as recommended by the manufacturer. Any personnel conducting an operation, servicing, or maintenance on a system or associated parts of the equipment should be trained and certified.
  • Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers, or liquid receivers) or piping should not be located in the proximity of heat sources, open flames, or operating the gas appliances,s or an operating electric heater.
  • The user/owner or their authorized representative shall regularly check the alarms, mechanical ventilation, and detectors, at least once a year, whereas required by national regulations, to ensure their correct functioning.
  • A logbook shall be maintained. The results of these checks shall be recorded in the logbook.
  • In case of ventilation in occupied spaces shall be checked to confi rm no obstruction.
  • Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certified operating personnel is instructed on the basis of the instruction manual about the construction,  supervision, operation, and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and handling of the refrigerant used.
  • The general requirement of trained andcertifi ed personnel are indicated as below:
    a) Knowledge of legislation, regulations, and standards relating to flammable refrigerants; and,
    b) Detailed knowledge of and skills in handling flammable refrigerants, personal protective equipment, refrigerant leakage prevention, handling of cylinders, charging, leak detection, recovery, and disposal; and,
    c) Able to understand and to apply in practice the requirements in the national legislation, regulations, and standards; and,
    d) Continuously undergo regular and further training to maintain this expertise.
    e) Air-conditioner piping in the occupied space shall be installed in such a way as to protect against accidental damage in operation and service.
    f) Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping.
    g) Ensure protection devices, refrigerating piping, and fittings are well protected against adverse environmental effects (such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris).
    h) Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted and guarded) to minimize the likelihood of hydraulic shock damaging the system.
    i) Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities.
    j) To ensure no leaking, field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa). No leak shall be detected.

Installation (Space)

  • Products with flammable refrigerants shall be installed according to the minimum room area, Amin (m²) mentioned in Table A of the Installation Instructions.
  • In the case of fi eld charge, the effect on refrigerant charge caused by the different pipe lengths has to be quantifi ed, measured, and labeled.
  • Must ensure the installation of pipe-work shall be kept to a minimum. Avoid using dented pipes and do not allow acute bending.
  • Must ensure that pipe-work shall be protected from physical damage.
  • Must comply with national gas regulations, state municipal rules, and legislation. Notify relevant authorities in accordance with all applicable regulations.
  • Must ensure mechanical connections be accessible for maintenance purposes.
  • In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
  • When disposal of the product, do follow the precautions in #12 and comply with national regulations.
    Always contact to local municipal offices for proper handling.

Servicing

2-1. Service personnel

  • The system is inspected, regularly supervised, and maintained by trained and certifi ed service personnel who is employed by the person user or party responsible.
  • Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant-containing parts are installed.
  • Ensure the refrigerant charge does not leak.
  • Any qualifi ed person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with industry-recognized assessment specifi cation.
  • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  • Servicing shall be performed only as recommended by the manufacturer.

2-2. Work

  • Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the precautions in #2-2 to #2-8 must be followed before conducting work on the system.
  • Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.
  • All maintenance staff and others working in the local area shall be instructed and supervised on the nature of the work being carried out.
  • Avoid working in confi ned spaces. Always ensure away from the source, at least 2 meters of safety distance, or zoning of free space area of at least 2 meters in radius.
  • Wear appropriate protective equipment, including respiratory protection, as conditions warrant.
  • Keep all sources of ignition and hot metal surfaces away.

2-3. Checking for the presence of refrigerant

  • The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres.
  • Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non sparking, adequately sealed, or intrinsically safe.
  • In case leakage/spillage happened, immediately ventilate the area and stay upwind and away from spill/release.
  • In case leakage/spillage happened, do notify persons downwind of the leaking/ spill, isolate the immediate hazard area and keep unauthorized personnel out.

2-4. Presence of fi re extinguisher

  • If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available at hand.
  • Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

2-5. No ignition sources

  • No person carrying out work in relation to a refrigerating system that involves exposing any pipework that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. They must not be smoking when carrying out such work.
  • All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removal, and disposal, during
    which flammable refrigerant can possibly be released to the surrounding space.
  • Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.
  • “No Smoking” signs shall be displayed.

2-6. Ventilated area

  • Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work.
  • A degree of ventilation shall continue during the period that the work is carried out.
  • The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

2-7. Checks to the refrigerating equipment

  • Where electrical components are being changed, they shall be fi t for the purpose and to the correct specifi cation.
  • At all times the manufacturer’s maintenance and service guidelines shall be followed.
  • If in doubt consult the manufacturer’s technical department for assistance.
  • The following checks shall be applied to installations using flammable refrigerants.
    – The actual refrigerant charge is in accordance with the room size within which the refrigerant-containing parts are installed.
    – The ventilation machinery and outlets are operating adequately and are not obstructed.
    – If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
    – Marking the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
    – Refrigerating pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant-containing components unless the components are constructed of materials that are inherently resistant to being corroded or are properly protected against being so corroded.

2-8. Checks to electrical devices

  • Repair and maintenance of electrical components shall include initial safety checks and component inspection procedures.
  • Initial safety checks shall include but are not limited to:
    – That capacitor is discharged: this shall be done in a safe manner to avoid the possibility of sparking.
    – That there are no live electrical components and wiring are exposed while charging, recovering, or purging the system.
    – That there is continuity of earth bonding.
  • At all times the manufacturer’s maintenance and service guidelines shall be followed.
  • If in doubt consult the manufacturer’s technical department for assistance.
  • If a fault exists that could compromise the safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
  • If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
  • The owner of the equipment must be informed or reported so all parties are advised thereinafter.

Repairs sealed components

  • During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
  • If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
  • Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, an excessive number of connections, terminals not made to original specifi cation, damage to seals, incorrect fitting of glands, etc.
  • Ensure that the apparatus is mounted securely.
  • Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres.
  • Replacement parts shall be in accordance with the manufacturer’s specifi cations.
    NOTE: The use of silicone sealant may inhibit the effectiveness of some types of leak detection equipment.
    Intrinsically safe components do not have to be isolated prior to working on them.

Repair intrinsically safe components

  • Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and currently permitted for the equipment in use.
  • Intrinsically safe components are the only types that can be worked on while living in the presence of a flammable atmosphere.
  • The test apparatus shall be at the correct rating.
  • Replace components only with parts specifi ed by the manufacturer. Unspecifi ed parts by the manufacturer may result in the ignition of refrigerant in the atmosphere from a leak.

Cabling

  • Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects.
  • The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

Detection of flammable refrigerants

  • Under no circumstances shall potential sources of ignition be used in the searching or detection of refrigerant leaks.
  • A halide torch (or any other detector using a naked flame) shall not be used.

The following leak detection methods are deemed acceptable for all refrigerant systems

  • No leaks shall be detected using detection equipment with sensitivity to detect leakage of 5g/year of refrigerant or better under a pressure of at least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa), for example, a universal sniffer.
  • Electronic leak detectors may be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need re-calibration.
    (Detection equipment shall be calibrated in a refrigerant-free area.)
  • Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
  • Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
  • Leak detection fluids are also suitable for use with most refrigerants, for example, bubble method and fluorescent method agents. The use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
  • If a leak is suspected, all naked flames shall be removed/extinguished.
  • If leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered from the system, or isolated (by means of shut-off valves) in a part of the system remote from the leak. The precautions in #8 must be followed to remove the refrigerant.

Removal and evacuation

  • When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used.
    However, it is important that best practice is followed since flammability is a consideration.
    The following procedure shall be adhered to: remove refrigerant -> purge the circuit with inert gas -> evacuate -> purge with inert gas -> open the circuit by cutting or brazing.
  • The refrigerant charge shall be recovered into the correct recovery cylinders.
  • The system shall be purged with OFN to render the appliance safe.
  • This process may need to be repeated several times.
  • Compressed air or oxygen shall not be used for this task.
  • Purging shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally pulling down to a vacuum.
  • This process shall be repeated until no refrigerant is within the system.
  • When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
  • This operation is absolutely vital if brazing operations on the pipework are to take place.
  • Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available.

OFN = oxygen-free nitrogen, a type of inert gas.

Charging procedures

  • In addition to conventional charging procedures, the following requirements shall be followed.
    – Ensure that contamination of different refrigerants does not occur when using charging equipment.
    – Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
    – Cylinders shall be kept in an appropriate position according to the instructions.
    – Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
    – Label the system when charging is complete (if not already).
    – Extreme care shall be taken not to over fill the refrigerating system.
  • Prior to recharging the system, it shall be pressure tested with OFN (refer to #7).
  • The system shall be leak tested on completion of charging prior to commissioning.
  • A follow-up leak test shall be carried out prior to leaving the site.
  • An electrostatic charge may accumulate and create a hazardous condition when charging and discharging the refrigerant. To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.

Decommissioning

  • Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
  • It is recommended good practice that all refrigerants are recovered safely.
  • Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
  • It is essential that electrical power is available before the task is commenced.
    a) Become familiar with the equipment and its operation.
    b) Isolate system electrically.
    c) Before attempting the procedure ensure that:
  • mechanical handling equipment is available, if required, for handling refrigerant cylinders;
  • all personal protective equipment is available and being used correctly;
  • the recovery process is supervised at all times by a competent person;
  • recovery equipment and cylinders conform to the appropriate standards.
    d) Pump down the refrigerant system, if possible.
    e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
    f) Make sure that the cylinder is situated on the scales before recovery takes place.
    g) Start the recovery machine and operate in accordance with instructions.
    h) Do not over fi ll cylinders. (No more than 80 % volume liquid charge).
    i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
    j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and all isolation valves on the equipment are closed off.
    k) Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.
  • An electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant. To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.

Labeling

  • Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant.
  • The label shall be dated and signed.
  • Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

Recovery

  • When removing refrigerants from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
  • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
  • Ensure that the correct number of cylinders for holding the total system charge is available.
  • All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
  • Cylinders shall be complete with a pressure relief valve and associated shut-off valves in good working order.
  • Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
  • The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
  • In addition, a set of calibrated weighing scales shall be available and in good working order.
  • Hoses shall be complete with leak-free disconnect couplings and in good condition.
  • Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained, and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult the manufacturer if in doubt.
  • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
  • Do not mix refrigerants in recovery units and especially not in cylinders.
  • If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not
    remain within the lubricant.
  • The evacuation process shall be carried out prior to returning the compressor to the suppliers.
  • Only electric heating to the compressor body shall be employed to accelerate this process.
  • When oil is drained from a system, it shall be carried out safely.

How to Use

To adjust airfl ow direction

  • Do not adjust the fl ap by hand.
    * For details operation, refer “To Learn More….”

To adjust FAN SPEED and QUIET condition

FAN SPEED:

  • When AUTO FAN is selected, the fan speed is adjusted automatically according to the operation mode.

QUIET:

  • This operation reduces airfl ow noise.

To switch between POWERFUL/ECO

POWERFUL:
To reach the desired temperature quickly

  • This operation is automatically stopped after 20 minutes.

ECO:

  • To reduce power consumption for better energy saving without sacrifi icing comfort.

To enjoy a fresher and cleaner environment

  • This operation combines both nanoe™X and nanoe™-G (nanoe™ TECHNOLOGY).
  • nanoe™ TECHNOLOGY automatically starts when the unit is turned on.
  • Press to turn ON or OFF this operation manually.
  • This operation can be activated even when the unit is OFF. Note that the fl ap and fan speed will operate according to the remote control setting.
  • If a power failure occurs during this operation, this operation resumes immediately when power resumes.

To connect to a network

  • For Wireless LAN Module operation setup, please refer to Setup Instructions Manual.

To maximize comfort while sleeping

  • This operation provides you with a comfortable environment while sleeping. It will automatically adjust the sleep pattern temperature during the activation period.
  • The indoor unit indicator will dim when this operation is activated. This is not applicable if the indicator brightness has been manually dimmed.
  • This operation is incorporated with the activation timer (0.5, 1, 2, 3, 4, 5, 6, 7, 8, or 9 hours).
  • This operation can be set together with a timer. Sleep operation has priority over OFF timer.
  • This operation can be canceled by pressing the respective button until the sleep timer reaches 0.0h.

To set the timer
You can set the timer to turn on and off the unit at 2 different preset times.

  • To cancel the timer, press ON or OFF to select the respective setting, then press CANCEL.
  • If the timer has been canceled manually or due to power failure, you can restore the timer again. Press ON or OFF to select the respective setting 1 or 2, then press SET.
  • The nearest timer setting is displayed and will activate in sequence.
  • The timer operation follows the clock setting on the remote control and will repeat daily when the timer has been set.
    For clock setting, refer to Quick Guide.

Note

To Learn More…

Operation mode
AUTO: The POWER indicator blinks at the initial stage.
The unit will select an operation mode depending on the room temperature.
COOL: Provides effi client comfort cooling to suit your needs.
DRY: Operates at low fan speed for a gentle cooling operation.

Energy-saving temperature setting
You may save energy when operating the unit within the recommended temperature range.
COOL : 26.0 °C ~ 28.0 °C / 79 °F ~ 82 °F.

Air flow direction

In COOL/DRY mode:
The horizontal flap is fixed at the middle position setting.
Once the temperature is achieved, the horizontal fl ap swings up/down automatically
In COOL/DRY mode:
The horizontal fl ap swings up/down automatically.

Auto-restart control
When power is resumed after a power failure, the operation will restart automatically with the last operation mode and airfl ow direction.

  • This control is not applicable when TIMER is set.

nanoe™X filter deactivation
Depending on the unit’s accumulated operation time, the nanoe™X may be activated only once a day after the unit is turned off in standby mode. During the nanoe™X filter deactivation operation, the flap will open slightly with low fan speed operation for 2.5 hours if the unit was in COOL/DRY mode, and 2 hours if the unit was in nanoe™ TECHNOLOGY before the unit is turned off. This is to remove viruses/bacteria from the surroundings.
The filter deactivation operation is complete when the fan stops and the flap closes. Do not turn off the power supply during this operation. After a power failure, this operation will not resume.

Operating conditions
Use this air conditioner in the temperature range indicated in the table.

Temperature °C (°F) Indoor Outdoor
DBT WBT DBT WBT
COOL Max. 32 (89.6) 23 (73.4) 46 (114.8) 26 (78.8)
Min. 16 (60.8) 11 (51.8) 16 (60.8) 11 (51.8)

DBT: Dry bulb temperature, WBT: Wet-bulb temperature

Cleaning the Air Conditioner

Cleaning has to be carried out at regular intervals to ensure the unit is at optimal performance. A dirty unit may cause malfunction and you may retrieve “H 99” error code. Consult an authorized dealer.

  • Before cleaning, switch off the power supply and unplug the unit.
  • Do not touch the aluminum fin as the sharp parts may cause injury.
  • Do not use benzine, thinner, or scouring powder.
  • Use soap ( ≅ pH 7) or neutral household detergent only.
  • Do not use water hotter than 40 °C / 104 °F.

Indoor unit
Wipe the unit gently with a soft and dry cloth.
The coils and fans should be cleaned periodically by an authorized dealer.

Outdoor unit
Clean the debris that surrounds the unit.
Clear any blockage from the drainpipe.
Front panel

Wash gently and dry.
How to remove the front panel

  1. Raise up.
  2.  Slide the front panel to right A and pull out B.

Close it securely

  1. Hold horizontally.
  2. Match and push in.
  3. Close down.
  4. Press both ends and center of the front panel.

Indoor unit

nanoe™ -G Generator
Once every 2 weeks

  • Clean with a dry cotton bud.
  • Do not touch during operation.

Air filiters
Once every 2 weeks

  • Wash/rinse the filters gently with water to avoid damaging the surface.
  • Dry the filters thoroughly under a shade, away from fi re or direct sunlight.
  • Replace any damaged filters.

Remove air filter
Remove from the unit
Attach air filter
Insert into the unit

Troubleshooting

The following symptoms do not indicate malfunction.

Symptom Cause
DOWER indicator blinks before the unit is switched Dn. •This is the preliminary step to prepare for the TIMER operation after it has been set.
•When the Timer is set ON, the unit may start earlier (up to 15 minutes) before the actual set time to achieve the desired temperature on time.
TIMER indicator is always ON. •When Timer has been set, the Timer setting repeats daily.
The operation is delayed a few minutes after restarting. •The delay is a protection to the unit’s compressor.
The indoor fan stops occasionally during the automatic fan speed setting. •This is to help remove the surrounding odor.
The room has a peculiar odor. •This may be due to the damp smell emitted by the wall, carpet, furniture, or clothing.
Cracking sound during operation. •Changes in temperature caused the unit to expand and contract.
Water flowing sound during operation. •Refrigerant flow inside the unit.
Mist emerges from the indoor unit. •During cooling operation, the discharged cold air may condense to water vapor.
The outdoor unit emits water or steam. •During cooling operation, condensation occurs on cold pipes and the condensed water may drip from the outdoor unit.
Discoloration of some plastic parts. •Discoloration is subjected to the types of materials used in plastic parts. It is accelerated when exposed to heat, sunlight, UV light, or environmental factors.
After extended use, dust may cover the front panel, grilles, and the wall surrounding the unit. •The dust accumulation is due to the air purification effect of negative ions from nanoe™-G. Remove the dust regularly with a clean dampened cloth.
Soft buzzing sound from the indoor unit during nanoe™ TECHNOLOGY operation. •It is normal when the nanoe™ X generator is working. If you are concerned about the sound, cancel the nanoeTm TECHNOLOGY operation.
The Wireless LAN indicator is ON when the unit is OFF •The unit’s wireless LAN connection with the router has been activated.

Check the following before calling for servicing.

Symptom Check
Operation in COOL mode is not working efficiently. •Set the temperature correctly.
•Close all doors and windows.
•Clean or replace the filters.
•Clear any obstruction at the air inlet and air outlet vents.
Noisy during operation. •Check if the unit has been installed at an incline.
•Close the front panel properly.
The remote control does not work.
(Display is dim or transmission signal is weak.)
•Insert the batteries correctly.
•Replace weak batteries.
The unit does not work. •Check if the circuit breaker is tripped.
•Check if timers have been set.
The unit does not receive the signal from the remote control. •Make sure the receiver is not obstructed.
•Certain fluorescent lights may interfere with the signal transmitter. Consult an authorized dealer.
The nanoeTm TECHNOLOGY indicator at the indoor unit is not ON when nanoe™ TECHNOLOGY is activated. •Use the remote control to retrieve the error code and consult an authorized dealer.

When…
The remote control is missing or a malfunction has occurred

  1. Raise the front panel.
  2. Press AUTO OFF/ON once to use in AUTO mode.
  3. Press AUTO OFF/ON until you hear 1 beep, then release to use in forced COOL mode.
  4. Press AUTO OFF/ON again to turn off the unit.

The indicators are too bright

  • To dim or restore the indicators’ brightness on the unit, press on the remote for 5 seconds.

Conducting a seasonal inspection after an extended period of non-use

  • Check the batteries.
  • Check that there is no obstruction around the air inlets and outlet vents.
  • Use AUTO OFF/ON on the unit to select COOL mode. For details, refer to “The remote control is missing or a malfunction has occurred” above. After 15 minutes of operation, it is normal to have the following temperature difference between the air inlet and outlet vents:
    COOL: ≥ 8 °C / 14.4 °F

The units will not be used for an extended period

  • Activate nanoe™ TECHNOLOGY mode for 2~3 hours to remove any moisture left in the internal parts thoroughly. This is to prevent mold growth.
  • Turn off the power supply and unplug the unit.
  • Remove the batteries from the remote control.

NON SERVICEABLE CRITERIA
TURN OFF THE POWER SUPPLY AND UNPLUG THE UNIT. Then consult an authorized dealer in the following conditions:

  •  Abnormal noise during operation.
  • Water/foreign particles have entered the remote control.
  • Water is leaking from the indoor unit.
  • The circuit breaker switches off frequently.
  • The power cord becomes unnaturally warm.
  • The switches or buttons are not functioning properly.

How to retrieve error codes
If the unit stops and the TIMER indicator blinks, use the remote control to retrieve the error code.

  • For certain errors, you may restart the unit for limited operation if there are 4 beeps when the operation starts.
Diagnostic display Abnormality/Protection control
H 00 No memory of failure
H 11 Indoor/outdoor abnormal communication
H 12 Indoor unit capacity unmatched
H 14 Indoor intake air temperature sensor abnormality
H 15 Outdoor compressor temperature sensor abnormality
H 16 Outdoor current transformer (CT) abnormality
H 17 Outdoor suction temperature sensor abnormality
H 19 Indoor fan motor mechanism lock
H 21 Indoor float switch operation abnormality
H 23 Indoor heat exchanger temperature sensor 1 abnormality
H 24 Indoor heat exchanger temperature sensor 2 abnormality
H 25 Indoor ion device abnormality
H 26 Minus ION abnormality
H 27 Outdoor air temperature sensor abnormality
H 28 Outdoor heat exchanger temperature sensor 1 abnormality
H 30 Outdoor discharge pipe temperature sensor abnormality
H 31 Abnormal swimming pool sensor
H 32 Outdoor heat exchanger temperature sensor 2 abnormality
H 33 Indoor/outdoor misconnection abnormality
H 34 Outdoor heat sink temperature sensor abnormality
H 35 Indoor/outdoor water adverse current abnormality
H 36 Outdoor gas pipe temperature sensor abnormality
H 37 Outdoor liquid pipe temperature sensor abnormality
H 38 Indoor/outdoor mismatch (brand code)
H 39 Abnormal indoor operating units or standby units
H 41 Abnormal wiring or piping connection
H 50 Ventilation fan motor locked
H 51 Ventilation fan motor locked
H 52 Left-right limit switch fixing abnormality
H 58 Indoor gas sensor abnormality
H 59 Eco sensor abnormality
H 64 Outdoor high-pressure sensor abnormality
H 67 nanoe™ abnormality
H 70 Light sensor abnormality