Honeywell Commercial Touchscreen Thermostat User Manual

Honeywell Commercial Touchscreen Thermostat User Manual

APPLICATION

TC500A-N/TC500B-NThermostat is an advanced, configurable, connected device for commercial buildings. It controls and monitors RTU, AHU, Heat Pump equipment, and their configurations. This device communicates over Wi-Fi, Bluetooth, BACnet IP, Sylk, easily integrates with the building automation system.

The built-in intelligent control algorithms of the device help to achieve the perfect balance between Energy Efficiency and Comfort. The device is packaged with numerous presets suitable for most commercial building requirements that enable the easy and quick initial setup.

The firmware of the device can be upgraded via Wi-Fi network. The device has four universal terminals and a pair of Sylk terminals to connect with sensors or other accessories. It also has a built-in temperature sensor, humidity sensor, and proximity sensor.

FEATURES

  • The device can be easily commissioned through Deploy app after connected to Gateway.
  • Easily customizable and intuitive UI.
  • Supports BACnet system schedule and holiday configuration.
  • Multiple, configurable, levels of user privilege access for features such as Reminders, Occupancy set points, Date/Time, Schedules, Calendars of special events, remote and local Manual Override, remote and local Occupancy Override, Choice of language and units, and so on.
  • Multiple, configurable, screen lockouts to prevent unauthorized settings changes.
  • High level control algorithms such as Auto Changeover, Adaptive Intelligent Recovery, Pre-occupancy Purge, Power up disable time, Freeze protection, and Demand limit controls are supported.
  • Settings to switch Fahrenheit to Celsius and vice-versa.
  • Auto display sleep to save energy when there is no user action for configured time out.
  • A LED indicator to show the operational status of the thermostat when the display goes to sleep mode.
  • Real-Time Clock time keeping accuracy with 72 hour retention during power loss.

Equipment Control Features 

  • 4H/3C Heat Pump, 3H/3C Conventional and modulating heat system
  • Constant speed Fan, 2-speed Fan, and Variable Speed Fan Packaged Economizer Coordination Output
  • Multiple Dehumidification and Humidification options
  • Service mode to manually command the outputs to test the operation of the mechanical equipment
  • Auto mode to switch between heating and cooling according to the current space temperature
  • Staging control, PID Tuning, CPH, OAT Lockout, DAT Lockout, Modulating control
  • Demand Limit Control to save energy
  • System Switch Options
  • Smoke Monitor

TECHNICAL SPECIFICATIONS

Power Characteristics 

Table 1. Power Characteristics 

Power Supply Rated voltage: 24VAC 50/60Hz,

Working voltage range: 20-30VAC, UL listed class-2 transformer or IEC 61558 listed transformer.

Power Consumption (Display ON) Max. 8.5VA @ 24VAC (355mA @ 24VAC)
Min. Load 8VA (all BOs OFF)
Max. Load 96VA (all BOs ON)

Display

Table 2. Display 

Display Type 24 BPP TFT display with CTP
Resolutions 480×480 pixel
Active Display Area 4” diagonally
Backlight LCD (Dimmable)

IO Characteristics 

Table 3. IO Characteristics 

UIO x 2
  • Resistive Input
    • For 10K NTC type II, C7021 series
    • For 10K NTC type III,C7023 series
    • For 20K NTC, TR21 and C7041 series.
  • ±0.5°C (±1°F) at 10 – 32°C (50 – 90°F)
  • ±1.1°C (±2°F) at -1.1 – 50°C (30 – 122°F)
  • Voltage Input, SELV
    • 0-10V, ±5% of full scale
  • Digital Input
    • Dry contact closure
    • Open circuit (≥ 100Kohms)
    • Closed circuit (≤100ohms)
  • Voltage Output
    •  0-10V, ±3% of full scale @2K ohms
UI x 2
  •   Resistive Input
    • for 10K NTC type II, C7021 series
    • for 10K NTC type III,C7023 series
    • for 20K NTC, TR21 and C7041 series
  • ±0.5°C (±1°F) at 10 – 32°C (50 – 90°F)
  • ±1.1°C (±2°F) at -1.1 – 50°C (30 – 122°F)
  • Voltage Input, SELV
    • 0-10V, ±5% of full scale
  • Digital Input
    • Dry contact closure
    • Open circuit (≥ 100Kohms)
    • Closed circuit (≤100ohms)
DO (G, Y1,Y2,Y3,W1,W2

,W3)

  • Relay Output
    • 1 Amps Max. at 24VAC
DO (AUX)
  • Relay Dry Contact
    •  1 Amps Max. at 24VAC/DC

Operating Environment

Table 4. Operating Environment 

Ambient Operating Temperature 32 to 122 °F (0 to +50°C)
Ambient Operating Humidity 10 to 90% relative humidity (non- condensing)
Storage Temperature -40 to 150 °F(-40 to 65.5°C)
Protection Class IP20

Compliances

Table 5. Compliances 

Certificates CE, FCC, ICES, UL/cUL, RoHs, REACH, Title 24, BTL, ASHRAE, LEED, and Prop65.
Standards EN 60730-1, EN 60730-2-9, EN 301489-1, EN 301489-17, EN 300328, EN 301893, EN 62479, UL60730-1, UL60730-2-9, Title 47 part 15 subpart B, Title 47 part 15 subpart C, RSS 210, ICES-003

Communication Baud Rates 

BACnet IP Over Wi-Fi
Wi-Fi 802.11 b/g/n
Bluetooth BLE 4.2 with 1 Mbps Classic Bluetooth with max. 3 Mbps

Electrical Characteristics 

Table 6. Electrical Characteristics 

Rated Impulse Voltage 500 V
Construction of Control Independently Mounted Control
Operation Method Type 1 Action
Pollution Degree 2
Purpose of Control Operating Control

Supported Sensors and Devices 

  • Indoor/Outdoor Air Temp Sensor
  • Discharge sensor/Supply air sensor
  • CO2 sensor
  • Mixed air sensor
  • Occupancy sensor
  • Dirty filter
  • Proof of airflow
  • Proof of waterflow
  • Sylk Sensor Bus devices (TR40 series and C7400S)
  • Up to four TR40 series room sensors
  • Up to two C7400S duct sensors

Terminal Identification 


Fig. 1. Terminals 

Table 7. Terminal identification 

Terminal Label Connection
24VAC R 24VAC power from heating transformer
C 24VAC common (Neutral). For 2 transformer systems, use common wire from cooling transformer
UIO1 1 Universal input/output
COM Common
UIO2 2 Universal input/output
COM Common
UI1 1 Universal input
COM Common
UI2 2 Universal input
COM Common
Sylk Sylk bus, master, power output
Sylk bus, master, power output
RS485 + BACnet Communications
_ BACnet Communications
R-RC Jumper between R and RC for single transformer system

Table 7. Terminal identification 

Terminal Label Connection
24VAC RC 24VAC power from cooling transformer
G Fan
Y1 Relay output, Compressor contactor (stage1)
Y2 Relay output, Compressor contactor (stage2)
Y3 Relay output, Compressor contactor (stage3)/Configurable Output
W1 Relay output, Heat (stage1)
W2 Relay output, Heat (stage2)
W3 Relay output, heat (stage3)/Configurable Output
Aux Relay dry contact, Aux-1
Relay dry contact, Aux-2

Thermostat Ordering Part Numbers

Table 8. Thermostat Part Numbers

TC500A-N/TC500B-N Thermostat with North American conformance
/ /

DIMENSIONS

GENERAL SAFETY INFORMATION

  • When performing any work (installation, mounting, start-up), all manufacturer instructions and in particular the Installation and Commissioning Instructions (MU1B-0208IE10) are to be observed.
  • TC500A-N/TC500B-N Thermostat may be installed and mounted only by authorized and trained personnel.
  • Rules regarding electrostatic discharge should be followed.
  • TC500A-N/TC500B-N Thermostat is modified in any way, except by the manufacturer, all warranties concerning operation and safety are invalidated.
  • Make sure that the local standards and regulations are observed at all times.
  • Use only accessory equipment which comes from or has been approved by Honeywell.
  • It is recommended that devices be kept at room temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate.
  • Investigated according to United States Standard UL60730-1, and UL60730-2-9.
  • Investigated according to Canadian National Standard(s) C22.2, No. 205-M1983 (CNL-listed).
  • Do not open TC500A-N/TC500B-N Thermostat, as it contains no user-serviceable parts inside!
  • CE declarations according to LVD Directive 2014/35/EU and EMC Directive 2014/30/EU.
  • Product standards are EN 60730-1 and EN 60730-2-9.
  • TC500A-N/TC500B-N Thermostat is Class B digital apparatus and complies with Canadian ICES-003.
  • This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
  • Caution: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
  • This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s licenceexempt RSS(s). Operation is subject to the following two conditions:
    1. This device may not cause interference.
    2. This device must accept any interference, including interference that may cause undesired operation of the device
  • This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause  harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
    • Reorient or relocate the receiving antenna.
    • Increase the separation between the equipment and receiver.
    • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
    • Consult the dealer or an experienced radio/TV technician for help.
  • To satisfy FCC&IC RF exposure requirements, a separation distance of 20 cm or more should be maintained between the antenna of this device and persons during device operation. To ensure compliance, operations at closer than this distance is not recommended.

Safety Information as per EN60730-1 

TC500A-N/TC500B-N Thermostat is intended for residential, commercial environments.

TC500A-N/TC500B-N Thermostat is an independently mounted electronic control system with fixed wiring.

TC500A-N/TC500B-N Thermostat is used for the purpose of building HVAC control and is suitable for use only in non-safety controls for installation on or in appliances.

Honeywell Building Solutions 

Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com

® U.S. Registered Trademark
© 2020 Honeywell International Inc. EN0B-0206 IE10 R0720