Honeywell PC3F2699IUF00 Hydronic Circulating 3 Speed Pump Datasheet
Honeywell PC3F2699IUF00 Hydronic Circulating 3 Speed Pump
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is designed for applications in closed-loop hydronic heating and cooling systems, as well as in solar-powered systems. The pump is non-submersible and for use in dry, frost-free, well-ventilated installations.
SPECIFICATIONS
Rate of flow: up to 34 gpm (128.7 lpm)
Pressure head: up to 31 ft (9 m)
Voltage: 115VAC +/-10% 60hz
Amperage: See “Speed switching” on page 2. Max. Pressure:
145 psi (at room temperature); 50 psi (at 200°F [93°C])
Temperature Range: Ambient temperature: 32°F to 104°F (0°C to 40°C) Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F
(93°C) with optional check valve installed]
Storage Temperature: -40°F to 100°F (-40° to 66°C)
Standards: Insulation Class F Temperature Class FT 95
L1 | L2 | L3 | L4 | L5 |
6.5 (165.5) | 6.1 (155) | 6.5 (165.5) | 7.75 (197) | 3.2 (80.2) |
Shipping weight: 9.5 lbs (4.32 Kg)
Materials
Component | Material |
Pump body | Cast iron |
Impeller | Polyamide |
Shaft | Ceramic |
Bearing | Ceramic |
Bearing plate | Stainless steel |
Can | Stainless steel |
Control: 3-step switch with manual speed selection
Motor protection
The motor includes an internal thermal overload protection. External motor protection is not required.
Speed switching
Three speed, with manual selector.
Speed | Volts | Amps | Watts |
1 | 115 |
1.09 | 125 |
2 | 1.52 | 175 | |
3 | 1.78 | 205 |
Flange Connections
Universal flange
Bolt hole spacing 3-5/32 in. (80.2 mm) Bolt holes 1/2 in. (12.7 mm)
Media
Clean water or water with up to 20% glycol. Up to 50% glycol may be used, but flow characteristics will differ from these specifications.
Optional and Replacement Parts
Check valves: PCV125
Flange gasket: PCG100
Table 1. Cross Reference for Pump Replacement
Honeywell | Grundfos | Taco | Bell & Gossett | Armstrong | Wilo | |||||
Model | Pump Length | Speed | Single Speed | 3-Speed | Single Speed | 3-Speed | Single Speed | 3-Speed | ||
PC3F2699IUF00 |
6.5” |
High | UP26-96F UP26-96F-FC UP26-116F UP26-116F-FC | UPS26-99 High UPS26-99-FC High | 0011F 0011F-IFC 0013F 0013F-IFC |
NRF-36 Med NRF-45 Med H-41 | E7 Astro 50 Astro 50-3 |
Star 30F Star 32F | S21 High | |
Medium | UP26-64F UP26-99FC | UPS26-99 Low UPS26-99-FC Low | 0014F 0014F-IFC |
Star 17 FX | S21 Med | |||||
Low | NRF-33 | Star S21 Low |
The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if information is found to be incorrect.
If the cross-referenced model uses a flow check valve, then use a flow check with the Honeywell model as well. Each Honeywell circulator replaces both regular and rotated flange models.
Automation and Control Solutions Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com