Philips DMC810GL Dynalite Multipurpose Controller Installation Guide

DMC810GL
Installation Instructions

Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.

Phase Control Ratings/Channel 
CH1 – CH4 Leading Edge

Output Ratings / Channel (CH)

Load Type CH5 – CH8
General Use 10 A 240 V∼
Incandescent 5 A 240 V∼
Magnetic with Halogen 2 A 240 V∼
Electronic Driver 3 A 240 V∼
Inrush Current 165 A∼

Output Ratings/Group
CH1 & CH5 ≤ 10 A
CH2 & CH6 ≤ 10 A
CH3 & CH7 ≤ 10 A
CH4 & CH8 ≤ 10 A
DMC810GL ≤ 40 A

Control Channel Ratings

DALI Broadcast ≤ 64/CH Guaranteed 128 mA, Maximum 250 mA Insulation: basic ≤ 200
DSI ≤ 64 / CH ≤ 200
1-10 V Sink 50 mA / Source 50 mA Driver dependent

Apply de-rating for electronic and LED loads.
The manufacturer is not responsible for dimmable lamp selection. Each lamp/dimmer combination must be tested for compatibility prior to installation.
This is a class A product. In a domestic environment, this product may cause radio interference, in which case the user may be required to take adequate measures.
Professional dimmers rated > 1000 W are out of scope of EN 61000-3-2.
© 2021 Signify Holding. All rights reserved. Specifications are subject to change without notice. No representation or warranty as to the accuracy or completeness of the nformation included herein is given and any liability for any action in reliance thereon is disclaimed. Philips and the Philips Shield Emblem have registered trademarks of  Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.

AZZ 477 0721 R15
www.lighting.philips.com/dynalite