SIEMENS SN1224L1125 Indoor Load Center Instructions

SIEMENS SN1224L1125 Indoor Load Center

RATINGS

125A MAXIMUM
BACK-FED MAIN BREAKER REQUIRES HOLD-DOWN MEANS AND LINE TERMINAL BARRIER. SEE ACCESSORY CHART FOR REQUIRED KIT(S).
120/240V∼, 60 HZ, 10 3W
208Y/120V∼, 60 HZ, 10 3W

FOR INSTALLATION BY A QUALIFIED PERSON IN ACCORDANCE WITH ALL LOCAL ELECTRICAL CODES AND/OR THE NATIONAL ELECTRICAL CODE ®

SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN MAIN BREAKER IS INSTALLED. WHEN USED AS SERVICE EQUIPMENT, APPLY “SERVICE DISCONNECT” LABEL(S) TO FRONT NEXT TO APPROPRIATE BREAKER HANDLE.

WHEN USED AS SERVICE EQUIPMENT, UNUSED NEUTRAL BAR TERMINALS MAY BE USED TO TERMINATE EQUIPMENT GROUNDING WIRES IN THE COMBINATIONS INDICATED FOR EQUIPMENT GROUND BAR TERMINALS.

SUM OF QT BREAKER RATING IS NOT TO EXCEED 110 AMPS PER BRANCH CIRCUIT BUS STAB.

TO RESET BREAKERS WITH TRIPPED HANDLE POSITION BETWEEN “ON” AND “OFF”, MOVE HANDLE TO “OFF” THEN TO “ON”.

REMOVE TWISTOUTS FROM TRIM ONLY WHERE BREAKERS WILL BE INSTALLED. ALL OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES.

THIS LOAD CENTER IS INVERTIBLE FOR BOTTOM FEED APPLICATIONS.

Siemens Industry, Inc. Norcross, Georgia U.S.A                                40901334 0101 Rev.01

IMPORTANT: DO NOT ALLOW PETROLEUM BASED (HYDROCARBON) SPRAYS, CHEMICALS, SOLVENTS OR ANY PAINT TO CONTACT INTERIOR COMPONENTS. PETROLEUM BASED CHEMICALS CAN CAUSE DEGRADATION OF ELECTRICAL INSULATING MATERIALS.

Hazardous Voltage.
Will cause death, serious injury or substantial property damage.
Turn off power supplying this equipment before working inside.

SHORT CIRCUIT CURRENT RATING

THIS PANELBOARD HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 100,000 AMPS RMS SYMMETRICAL, 120/240V~. THE ACTUAL RATING IS DEPENDENT ON THE BRANCH BREAKERS INSTALLED IN THIS PANELBOARD AND THE MAIN/FEEDER BREAKER, IF ANY, INSTALLED AHEAD OF THIS PANELBOARD. THE CORRECT MAIN BREAKER/FEEDER/MAIN BREAKER/BRANCH BREAKER SERIES COMBINATIONS TO BE USED ARE LISTED IN THE TABULATION BELOW. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED IN THIS PANELBOARD MUST BE MANUFACTURED BY SIEMENS AND MUST BE OF THE CORRECT TYPE AS INDICATED IN THE TABULATION BELOW. USE OF OTHER CIRCUIT BREAKERS IN THIS EQUIPMENT MAY VOID THE WARRANTY.

➊ NEUTRAL BUS FOR PLUG-ON NEUTRAL CIRCUIT BREAKERS
➋ BOND WHEN REQ’D
➌ BACK-FED BRKR WHEN USED

MAIN BREAKER (SIEMENS TYPE) MAIN/FEEDER BREAKER PANELBOARD MAIN BRANCH BREAKER RATING AMPS
NONE USED NONE USED NONE USED or QP OP, QG, QT, OTA, QTAN, OAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE2 QPH*, QAFH, QAFH2, QFGAH2, QPHF. QPHF2 QEH QEH2 10,000

 

 

22,000

NONE USED NONE USED
NONE USED EQ9677, QPH* NONE USED or QP, QPH* QP, QT, OTA, QTAN, QAF, QAFN, QAF2, QAF2N, QFGA2, QFGA2N, QPF, QPF2, QPF2N, QE, QE2
QPH, BLH, QSH
QSHH  

NONE USED or QP, QPH*

QP, QPH*, QT, OTA, QTAN, OAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF. QPHF2 OE, QE2 QEH, QEH2 HQP*, HQAF2, HQFGA2, HQPF2  

42,000

 

 

 

 

 

 

65,000

NONE USED NONE USED
HQP* QP, QPH*, QT, OTA, QTAN, OAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, QFGA2, QFGA2N, QFGAH2, QPF, QPF2, QPF2N, QPHF, QPHF2, QE, QE2, QEH, QEH2
ED4 ED6 HOP. HBL HOS NONE USED or QP, QPH*, HOP*
NDGA, NFGA QPH, BLH
JXD2(-A), JD6(-A), JXD6(-A), LD6(-A), LXD6(-A), MD6,
MXD6, ND6, SND6-B, NXD6, NJJA, NJGA, NLGB, NMG,
NNG, NPG, PD6, SPD6-B, PXD6, RD6, RXD6
QPH, BLH, as
FD6, FXD6 NONE USED or QP, BL, QS
ND6, SND6-B, NXD6, Class J, T, R, or L Fuses QPH, BLH
JXD2(-A), JDS(-A), JXDS(-A), LDS(-A), LXDS(-A), MDS, MXDS, NDS, SNDS-B, NXDS, PDS, SPDS-B, PXDS, RDS, RXDS, NDGA, NFGA, NJJA, NJGA, NLGB, NMG, NNG, NPG NONE USED QPH*, HOP*
NONE USED HQSH, HQPH, HED4, HEDS, NGB NONE USED or QP, QPH*, HOP* QP, QPH*, HQP*, QT, QTA, QTAN, QAF, QAFN, QAF2, QAF2N, QAFH, QAFH2, HQAF2, QFGA2, QFGA2N, QFGAH2, HQFGA2, QPF, QPF2, QPF2N, QPHF, QPHF2, HQPF2, QE, QE2, QEH2 100,000
HFD6, HFXD6, HFGA, HJD6( A), HJXD6~A), HJGA, HLD6(-A), HLXD6(-A), HLGB, HMD6, HM D6, HMG, HND6, SHND6-B, HNXD6, HNG, HPD6, SHPD6-B, HPXD6, HPG, HRD6, HRXD6, or Class J, T, R, or L Fuses ED4, EDS, as
H FD6, H FXD6, or 300V Class T Fuses – 200A Max NONE USED or QP, BL
HOGA, HFGA,or 300V Class T Fuses – 600A Max NONE USED orQPH, BLH NONE USED or QPH*, HOP* QPH*, HQP*

*Type QPH and HQP breakers installed in this panel are limited to 100 amps max. when installed on a circuit capable of delivering fault current greater than 10,000 amps.

TERNINAALS WIRE TORQUE
A, B, G, N1 2/0-4AWG 110 LB-INS
NEUTRALJGROUND BARS (USE TYPE EC1GB or EC2GB GND BAR KIT ACCESSOR 10-14 CU/10-12 AL BAWG 6-4AWG 20 LB-INS
25 LB-INS
35 LB-INS
GROUND CONDUCTORS ONLY (2)or(3) 14 AWG
2  12-10AWG
20 LB-INS
20 LB-INS
N2 ECLK2N NEUTRAL LUG 2/0-4AWG 110 LB-INS
ECLK1-2 NEUTRAL WG KIT ECLK2 NEUTRAL WG KIT 2/0-4AWG
2/0-4AWG
45 LB-INS
135 LB-INS
MAN WG TO BUS CONNECTION (1/4-20 NUT) 45 LB-INS
BONDING SCREW 45 LB-INS

USE COPPER OR AWMINUM 60°/75°C WIRE

SEE BREAKER MARKINGS FOR WIRE SIZE AND TORQUE REQUIREMENTS

ACCESSORIES

DESCRIPTION CAT. NO.
DOOR LOCK ECQFL2
FILLER PLATE, 1″ QF3
BREAKER HOLD-DOWN/BARRIER ECMBR2
SUBFEED WG KIT ECLK2125
100-125 AMP MAIN LUG KIT ECMLK125
STANDBY PWR INTERLOCK KIT ECSBPK01 ECSBPK02

Assembled in Mexico
© 2020 Copyright Siemens lndus1ry, Inc.
® The National Electrical Code is a registered trademark of the National Fire Protection Association.