ABB BDS0032 FusionAir Smart Sensor Installation Guide

ABB BDS0032 FusionAir Smart Sensor

DIMENSIONS

MOUNTING

  •  Install the FusionAir Smart Sensor on an easily accessible interior wall, approximately 60” (1.5 m) above the floor in an area of average temperature
  • Avoid direct sunlight or other heat sources (e.g. the area above radiators or other heat-emitting equipment)
  • Avoid locations behind doors, on outside walls and above or below air discharge grills and diffusers

IMPORTANT NOTICE AND SAFETY ADVICE 

This device is for use as an operating control. It is NOT a safety device. Where a device failure endangers human life and/or property, it is the responsibility of the client, installer, and system designer to add additional safety devices to prevent a system failure caused by such a device failure.
Ignoring specifications and local regulations may cause equipment damage and endangers life and property. Tampering with the device or misapplication will void warranty.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

WARNING: Changes or modifications not expressively approved by the party responsible for compliance could void the user’s authority to operate the equipment.

INSTALLATION

  1. Install a 4 core cable (maximum length 1,600 ft. / 500 m) from the associated controller sensor bus and sensor power connections to a flush-mounting wall box compatible with the mounting plate (see the previous page)
  2.  Connect the field controller to the terminals of the power case according to the wiring diagrams below. Set the address of the FusionAir device (see Addressing below).
  3. Attach the mounting plate to the flush-mounting box. Make sure the mounting screw heads do not stand out more than 0.2” (5 mm) off the surface of the mounting plate.
  4. Align the body of the FusionAir device with the clips on the mounting plate and press gently until the front part is fully connected.

ADDRESSING

Each FusionAir device connected on a controller’s Sensor bus must be assigned a unique address. This is set on the DIP switch visible on the back of the device

The address must be between 1 and the maximum number of FusionAir devices supported by the controller to which it is connected:

  • 1 …4 (e.g. CBX, CBV, CBT-2U1R, CBT-3T6-5R), or
  • 1 … 10 (e.g FBXi, CBXi, FBVi)

Note: The FusionAir device reads the dip switch settings when power is applied. Changing the DIP switch while it is running will not take effect until the device is unplugged and plugged back in.

WIRING
Single FusionAir per controller
Connect terminals 1…4 to the Sensor port on the CBX / CBXi / FLXeon controller.
Optionally connect terminals 5…7 to external digital signals such as Occupancy or Room Key Card.

Multiple FusionAir per controller
Daisy-chain terminals 1…4 as shown below.

Note: To allow for potential current requirements for multiple sensors when accent lights are used, it is recommended that the power lines
(terminals 1 and 2) are connected to the Controller’s 24 V power supply.

FA-T (Passive sensor)
The FA-T’s temperature sensor and side switch can be connected directly to 4 terminals on the Controller as shown, one analog input and one digital input.

Alternatively, they can be connected to a single analog input and logic in the Controller Strategy can derive the switch position.
The digital input is a push-button on the side of the FusionAir device and can be used for example to over-ride a schedule for 1hr or override until next value change.

©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM